11 kV and 33 kV distribution.

XLPE Cables (Copper & Aluminium, Armoured & Unarmoured)
XLPE insulated power cables, LT and HT up to 33 kV, copper and aluminium, armoured and unarmoured, to IS 7098.
- Voltage
- 1.1 kV; 3.3/3.3, 6.35/11, 12.7/22, 19/33 kV
- Conductor
- Copper or aluminium, compacted stranded
- Temperature
- 90 °C continuous, 250 °C short circuit
- Armour
- GI strip/wire; aluminium wire for single-core
Buying several items? Upload your BOQ
- Electrical supply since 1991
- Leading makes, or the one you specify
- GST invoice · delivery across India
About XLPE Cables (Copper & Aluminium, Armoured & Unarmoured)
XLPE (cross-linked polyethylene) insulation operates continuously at 90 °C and withstands 250 °C on short circuit, so an XLPE cable carries more current than a PVC cable of the same size. LT cables follow IS 7098-1; HT cables (3.3–33 kV) follow IS 7098-2 with conductor and insulation screens.
Compare in the XLPE vs PVC guide. Terminate HT cables with heat-shrink kits per the LT vs HT termination guide and double compression glands.
Aluminium conductor versions are on aluminium armoured cables.
- 90 °C ratedHigher current than PVC.
- LT and HT1.1 kV to 33 kV.
- Cu and AlArmoured or unarmoured.
- Five makesPolycab, KEI, Havells, Finolex, RR Kabel.
Specifications
| Voltage | 1.1 kV; 3.3/3.3, 6.35/11, 12.7/22, 19/33 kV |
|---|---|
| Conductor | Copper or aluminium, compacted stranded |
| Temperature | 90 °C continuous, 250 °C short circuit |
| Armour | GI strip/wire; aluminium wire for single-core |
| Sheath | PVC ST2, FRLS options |
| Standards | IS 7098-1, IS 7098-2 |
Applications
Transformer to PCC.
Plant and project cabling.
How to choose
- Voltage grade
Earthed or unearthed system grade.
- Size and conductor
By current, fault level and drop.
- Armour
Single-core needs non-magnetic armour.
XLPE vs PVC
| Property | XLPE | PVC |
|---|---|---|
| Max conductor temp | 90 °C | 70 °C |
| Short-circuit temp | 250 °C | 160 °C |
| Voltage | LT and HT | Mostly LT |
| Current per size | Higher | Lower |
Frequently asked questions
Why aluminium armour on single-core cables?
Steel armour on single-core AC cables heats from induced currents; aluminium is non-magnetic.
What does 6.35/11 kV mean?
Rated 6.35 kV to earth and 11 kV between phases, for earthed systems.
What size cable do I need?
Size by current rating after derating for grouping, ambient temperature and laying method, then check voltage drop and short-circuit rating. Send load, length and laying method and we will check it.
Industries that use XLPE Cables (Copper & Aluminium, Armoured & Unarmoured)
HT distribution.
Transformer and PCC feeders.
Get a quote for XLPE Cables (Copper & Aluminium, Armoured & Unarmoured)
Tell us the grade, size, form and quantity, or attach a drawing, BOQ or photo of the existing item. We reply with a line-by-line quotation from Kolkata, with delivery across India.
- Send your requirement Grade, size, quantity, or a BOQ, drawing or photo.
- We confirm and quote Matching make and grade, price and dispatch date, line by line.
- Dispatch from Kolkata With GST invoice, delivered to your site across India.