Main contact resistance of ACB, VCB and SF₆ breakers.

Testing & Measuring Instruments
Micro-Ohm Meter / Low Resistance Measuring Bridge
Micro-ohm meters and low resistance bridges (10 A–600 A DC) for breaker contacts, busbar joints and windings.
- Test current
- 10 A, 100 A, 200 A, 600 A DC
- Range
- 0.1 µΩ to Ω, by current
- Method
- 4-wire Kelvin, ripple-free DC
- Winding mode
- Inductive load safe discharge on winding models
Buying several items? Upload your BOQ
- Electrical supply since 1991
- Leading makes, or the one you specify
- GST invoice · delivery across India
About Micro-Ohm Meter / Low Resistance Measuring Bridge
A micro-ohm meter passes a high DC current through a joint or contact and measures the voltage drop with separate 4-wire Kelvin leads, giving resistance in micro-ohms. It is the standard test for circuit breaker main contacts, busbar joints, cable joints and transformer windings.
IEC 62271-1 calls for a DC test current of at least 50 A for breaker contact resistance, and 100 A or more is common practice; high current breaks through surface films that a low current would misread. The micro-ohm meter selection guide explains current and range choices; for a simpler mV-drop method see the millivolt drop test set.
- 10 A to 600 A DCHigh test current for true contact resistance.
- µΩ resolution0.1 µΩ on high-current models.
- Kelvin 4-wireLead resistance cancelled.
- Three makesMegger, Motwane and Hioki.
Specifications
| Test current | 10 A, 100 A, 200 A, 600 A DC |
|---|---|
| Range | 0.1 µΩ to Ω, by current |
| Method | 4-wire Kelvin, ripple-free DC |
| Winding mode | Inductive load safe discharge on winding models |
| Practice | IEC 62271-1 contact resistance (≥ 50 A DC; 100 A common) |
Applications
Bolted and welded joint quality.
Winding resistance.
- Power & utilities
- Motor & transformer rewinding
- Manufacturing & engineering
- Steel & metals
- Switchgear makers
- Transformer manufacturers
How to choose
- Test current
100 A minimum for breakers; 200–600 A for large switchgear.
- Inductive loads
Winding-rated models for transformers.
- Portability
Weight and battery vs mains for field use.
Makes we can quote
Quoted in the makes below and any other make on your approved list.
Frequently asked questions
Why use 100 A or more?
Higher current (IEC 62271-1 sets a 50 A minimum) breaks through oxide films and gives a true contact resistance reading.
What is a typical breaker contact resistance?
Usually tens of micro-ohms; compare with the maker’s value and previous results.
Industries that use Micro-Ohm Meter / Low Resistance Measuring Bridge
Breaker and busbar maintenance.
Busbar joint checks before dispatch.
Get a quote for Micro-Ohm Meter / Low Resistance Measuring Bridge
Tell us the grade, size, form and quantity, or attach a drawing, BOQ or photo of the existing item. We reply with a line-by-line quotation from Kolkata, with delivery across India.
- Send your requirement Grade, size, quantity, or a BOQ, drawing or photo.
- We confirm and quote Matching make and grade, price and dispatch date, line by line.
- Dispatch from Kolkata With GST invoice, delivered to your site across India.