Kolkata · Since 1991Shipping across IndiaGST 19AESPK5930K1ZU
+91 82403 34928

Find your electrical requirement

Share an item reference or photo for help →
Insulation Resistance cum Polarising Index Test Kit product-type reference

Testing & Measuring Instruments

Insulation Resistance cum Polarising Index Test Kit

Insulation resistance testers (meggers) from 500 V to 15 kV, with polarisation index and DAR for motors, cables and transformers.

Test voltage
250 V–1 kV (handheld); 5, 10 and 15 kV (diagnostic)
Range
Up to 10 TΩ–30 TΩ on HV models
Diagnostics
PI, DAR, step voltage, dielectric discharge (model dependent)
Power
Battery, mains or hand-crank

Buying several items? Upload your BOQ

  • Electrical supply since 1991
  • Leading makes, or the one you specify
  • GST invoice · delivery across India

About Insulation Resistance cum Polarising Index Test Kit

An insulation resistance tester applies a stable DC test voltage and measures the leakage through insulation, reading in MΩ to TΩ. Polarisation index (10-minute/1-minute ratio) and dielectric absorption ratio (60 s/30 s) show whether insulation is dry and clean rather than giving a single spot value.

Pick the test voltage by equipment rating: 500 V–1 kV for LT motors and cables, 2.5–5 kV for HT motors and transformers, 10–15 kV for HV cables and generators. Read the IR vs PI guide before setting acceptance limits, and use a tan delta test set for deeper insulation diagnosis.

  • 500 V to 15 kVHandheld LV to HV diagnostic testers.
  • PI and DARTimed ratios for insulation condition.
  • Up to TΩ rangesFor HV cables and transformers.
  • Six makesMegger, Motwane, Fluke, Hioki, Rishabh and Kusam-Meco.

Specifications

Test voltage250 V–1 kV (handheld); 5, 10 and 15 kV (diagnostic)
RangeUp to 10 TΩ–30 TΩ on HV models
DiagnosticsPI, DAR, step voltage, dielectric discharge (model dependent)
PowerBattery, mains or hand-crank
StandardsIEEE 43 practice for rotating machines

Applications

Motors and generators

Winding IR and PI before energising.

Cables

LT and HT cable acceptance and periodic tests.

Transformers

Winding-to-winding and winding-to-earth IR.

How to choose

  1. Test voltage

    Match to equipment voltage: 1 kV for LT, 5 kV and above for HT.

  2. Range and diagnostics

    Need PI, DAR or step voltage? Choose a diagnostic model.

  3. Power and portability

    Battery handheld for field, mains units for workshops.

Test voltage by equipment

Test voltage by equipment
EquipmentTypical DC test voltage
LT motors, cables up to 1.1 kV500 V–1 kV
HT motors 3.3–6.6 kV2.5–5 kV
11 kV cables and transformers5–10 kV
33 kV cables, generators10–15 kV

Makes we can quote

Quoted in the makes below and any other make on your approved list.

Frequently asked questions

What is a good polarisation index?

For most rotating machines, IEEE 43 treats a PI of 2.0 or more as acceptable for class B and higher insulation; below 1.0 indicates a problem.

Is “megger” the same as an IR tester?

Megger is a brand name commonly used for any insulation resistance tester.

Which voltage for a 415 V motor?

Usually 500 V or 1 kV DC.

Industries that use Insulation Resistance cum Polarising Index Test Kit

Rewinding shops

IR and PI before dispatch of rewound motors.

Utilities

Transformer and cable maintenance testing.

Get a quote for Insulation Resistance cum Polarising Index Test Kit

Tell us the grade, size, form and quantity, or attach a drawing, BOQ or photo of the existing item. We reply with a line-by-line quotation from Kolkata, with delivery across India.

  1. Send your requirement Grade, size, quantity, or a BOQ, drawing or photo.
  2. We confirm and quote Matching make and grade, price and dispatch date, line by line.
  3. Dispatch from Kolkata With GST invoice, delivered to your site across India.
Prefer WhatsApp?
PDF, Excel, Word, CSV, images · 5 files · 4 MB
Add email or phone so we can reply.
Add company name (optional)
Files are sent privately to our sales team.