Winding IR and PI before energising.

Testing & Measuring Instruments
Insulation Resistance cum Polarising Index Test Kit
Insulation resistance testers (meggers) from 500 V to 15 kV, with polarisation index and DAR for motors, cables and transformers.
- Test voltage
- 250 V–1 kV (handheld); 5, 10 and 15 kV (diagnostic)
- Range
- Up to 10 TΩ–30 TΩ on HV models
- Diagnostics
- PI, DAR, step voltage, dielectric discharge (model dependent)
- Power
- Battery, mains or hand-crank
Buying several items? Upload your BOQ
- Electrical supply since 1991
- Leading makes, or the one you specify
- GST invoice · delivery across India
About Insulation Resistance cum Polarising Index Test Kit
An insulation resistance tester applies a stable DC test voltage and measures the leakage through insulation, reading in MΩ to TΩ. Polarisation index (10-minute/1-minute ratio) and dielectric absorption ratio (60 s/30 s) show whether insulation is dry and clean rather than giving a single spot value.
Pick the test voltage by equipment rating: 500 V–1 kV for LT motors and cables, 2.5–5 kV for HT motors and transformers, 10–15 kV for HV cables and generators. Read the IR vs PI guide before setting acceptance limits, and use a tan delta test set for deeper insulation diagnosis.
- 500 V to 15 kVHandheld LV to HV diagnostic testers.
- PI and DARTimed ratios for insulation condition.
- Up to TΩ rangesFor HV cables and transformers.
- Six makesMegger, Motwane, Fluke, Hioki, Rishabh and Kusam-Meco.
Specifications
| Test voltage | 250 V–1 kV (handheld); 5, 10 and 15 kV (diagnostic) |
|---|---|
| Range | Up to 10 TΩ–30 TΩ on HV models |
| Diagnostics | PI, DAR, step voltage, dielectric discharge (model dependent) |
| Power | Battery, mains or hand-crank |
| Standards | IEEE 43 practice for rotating machines |
Applications
LT and HT cable acceptance and periodic tests.
Winding-to-winding and winding-to-earth IR.
- Power & utilities
- Motor & transformer rewinding
- Manufacturing & engineering
- Steel & metals
- Infrastructure & construction
- Cable and transformer manufacturers
How to choose
- Test voltage
Match to equipment voltage: 1 kV for LT, 5 kV and above for HT.
- Range and diagnostics
Need PI, DAR or step voltage? Choose a diagnostic model.
- Power and portability
Battery handheld for field, mains units for workshops.
Test voltage by equipment
| Equipment | Typical DC test voltage |
|---|---|
| LT motors, cables up to 1.1 kV | 500 V–1 kV |
| HT motors 3.3–6.6 kV | 2.5–5 kV |
| 11 kV cables and transformers | 5–10 kV |
| 33 kV cables, generators | 10–15 kV |
Makes we can quote
Quoted in the makes below and any other make on your approved list.
Frequently asked questions
What is a good polarisation index?
For most rotating machines, IEEE 43 treats a PI of 2.0 or more as acceptable for class B and higher insulation; below 1.0 indicates a problem.
Is “megger” the same as an IR tester?
Megger is a brand name commonly used for any insulation resistance tester.
Which voltage for a 415 V motor?
Usually 500 V or 1 kV DC.
Industries that use Insulation Resistance cum Polarising Index Test Kit
IR and PI before dispatch of rewound motors.
Transformer and cable maintenance testing.
Get a quote for Insulation Resistance cum Polarising Index Test Kit
Tell us the grade, size, form and quantity, or attach a drawing, BOQ or photo of the existing item. We reply with a line-by-line quotation from Kolkata, with delivery across India.
- Send your requirement Grade, size, quantity, or a BOQ, drawing or photo.
- We confirm and quote Matching make and grade, price and dispatch date, line by line.
- Dispatch from Kolkata With GST invoice, delivered to your site across India.