Measure the load profile
A single power-factor reading cannot describe a variable industrial load. Review demand and power-factor trends across shifts before deciding the total kVAr and number of stages.
Check harmonic conditions
Non-linear loads such as drives and rectifiers can over-stress ordinary capacitor banks. A harmonic survey helps determine whether detuned reactors or filtered correction is required.
Choose the switching strategy
Conventional contactor switching suits slower load changes; thyristor switching is preferred where reactive demand changes rapidly and transient-free operation matters.
Estimate the correction kVAr
For an ideal steady load: Qc = kW × [tan(acos(present PF)) − tan(acos(target PF))].
Estimated correction: 42.1 kVAr
This is a starting estimate, not a final bank rating. Stage selection, harmonic distortion, voltage, reactor design and load variation need engineering review. Savings depend on your utility tariff and measured usage.
Send your load profile for an APFC quotation →Specify your requirement
Send the rating, make, quantity and delivery location. Attach the drawing or datasheet where available.
Request a quote
